WHAT IS A CLEAN ROOM?

Clean Room

Typically used in manufacturing or scientific research, a clean room is a controlled environment that has a low level of pollutants such as dust, airborne microbes, aerosol particles, and chemical vapors. To be exact, a clean room has a controlled level of contamination that is specified by the number of particles per cubic meter at a specified particle size. The ambient air outside in a typical city environment contains 35,000,000 particles per cubic meter, 0.5 micron and larger in diameter, corresponding to an ISO 9 clean room which is at the lowest level of clean room standards.

Clean Room Overview

Clean rooms are used in practically every industry where small particles can adversely affect the manufacturing process. They vary in size and complexity, and are used extensively in industries such as semiconductor manufacturing, pharmaceuticals, biotech, medical device and life sciences, as well as critical process manufacturing common in aerospace, optics, military and department of energy.

A clean room is any given contained space where provisions are made to reduce particulate contamination and control other environmental parameters such as temperature, humidity and pressure. The key component is the High Efficiency Particulate Air (HEPA) filter that is used to trap particles that are 0.3 micron and larger in size. All of the air delivered to a clean room passes through HEPA filters, and in some cases where stringent cleanliness performance is necessary, Ultra Low Particulate Air (ULPA) filters are used.
Personnel selected to work in clean rooms undergo extensive training in contamination control theory. They enter and exit the clean room through airlocks, air showers and /or gowning rooms, and they must wear special clothing designed to trap contaminants that are naturally generated by skin and the body.
Depending on the room classification or function, personnel gowning may be as limited as lab coats and hairnets, or as extensive as fully enveloped in multiple layered bunny suits with self contained breathing apparatus.
Clean room clothing is used to prevent substances from being released off the wearer's body and contaminating the environment. The clean room clothing itself must not release particles or fibers to prevent contamination of the environment by personnel. This type of personnel contamination can degrade product performance in the semiconductor and pharmaceutical industries and it can cause cross-infection between medical staff and patients in the healthcare industry for example.
Clean room garments include boots, shoes, aprons, beard covers, bouffant caps, coveralls, face masks, frocks/lab coats, gowns, glove and finger cots, hairnets, hoods, sleeves and shoe covers. The type of clean room garments used should reflect the clean room and product specifications. Low-level clean rooms may only require special shoes having completely smooth soles that do not track in dust or dirt. However, shoe bottoms must not create slipping hazards since safety always takes precedence. A clean room suit is usually required for entering a clean room. Class 10,000 clean rooms may use simple smocks, head covers, and booties. For Class 10 clean rooms, careful gown wearing procedures with a zipped cover all, boots, gloves and complete respirator enclosure are required.

Clean Room Air Flow Principles

Clean rooms maintain particulate-free air through the use of either HEPA or ULPA filters employing laminar or turbulent air flow principles. Laminar, or unidirectional, air flow systems direct filtered air downward in a constant stream. Laminar air flow systems are typically employed across 100% of the ceiling to maintain constant unidirectional flow. Laminar flow criteria is generally stated in portable work stations (LF hoods), and is mandated in ISO-1 through ISO-4 classified clean rooms.
Proper clean room design encompasses the entire air distribution system, including provisions for adequate, downstream air returns. In vertical flow rooms, this means the use of low wall air returns around the perimeter of the zone. In horizontal flow applications, it requires the use of air returns at the downstream boundary of the process. The use of ceiling mounted air returns is contradictory to proper clean room system design.

Clean Room Classifications

Clean rooms are classified by how clean the air is. In Federal Standard 209 (A to D) of the USA, the number of particles equal to and greater than 0.5µm is measured in one cubic foot of air, and this count is used to classify the clean room. This metric nomenclature is also accepted in the most recent 209E version of the Standard. Federal Standard 209E is used domestically. The newer standard is TC 209 from the International Standards Organization. Both standards classify a clean room by the number of particles found in the laboratory's air. The clean room classification standards FS 209E and ISO 14644-1 require specific particle count measurements and calculations to classify the cleanliness level of a clean room or clean area. In the UK, British Standard 5295 is used to classify clean rooms. This standard is about to be superseded by BS EN ISO 14644-1.
Clean rooms are classified according to the number and size of particles permitted per volume of air. Large numbers like "class 100" or "class 1000" refer to FED_STD-209E, and denote the number of particles of size 0.5 µm or larger permitted per cubic foot of air. The standard also allows interpolation, so it is possible to describe e.g. "class 2000."
Small numbers refer to ISO 14644-1 standards, which specify the decimal logarithm of the number of particles 0.1 µm or larger permitted per cubic metre of air. So, for example, an ISO class 5 clean room has at most 105 = 100,000 particles per m³.
Both FS 209E and ISO 14644-1 assume log-log relationships between particle size and particle concentration. For that reason, there is no such thing as zero particle concentration. Ordinary room air is approximately class 1,000,000 or ISO 9.

ISO 14644-1 Clean Room Standards

Class Maximum Particles/m3 FED STD 209EEquivalent
>=0.1 µm >=0.2 µm >=0.3 µm >=0.5 µm >=1 µm >=5 µm
ISO 1 10 2          
ISO 2 100 24 10 4      
ISO 3 1,000 237 102 35 8   Class 1
ISO 4 10,000 2,370 1,020 352 83   Class 10
ISO 5 100,000 23,700 10,200 3,520 832 29 Class 100
ISO 6 1,000,000 237,000 102,000 35,200 8,320 293 Class 1,000
ISO 7       352,000 83,200 2,930 Class 10,000
ISO 8       3,520,000 832,000 29,300 Class 100,000
ISO 9       35,200,000 8,320,000 293,000 Room Air